YamBMS charging logic
Note
Please read the documentation regarding the charging settings.
Note
Please read the YamBMS 1.7.1 Cut-Off charging logic release note.
Charging Logic Diagram
The charging voltage and current correspond to the default values in the YAML script and can be modified.
Cut-Off Charging Logic Equation
Source: Charging Marine Lithium Battery Banks
Special thanks to @shvmm for deriving the equations.
Note: The equations below can be adopted for other chemistries like Li-ion and LTO with specific CVmin and CVmax values.
The physical anchor of the equation is CVmin, the resting voltage of a fully charged cell (~3.37 V for LFP): a cell above cv_min at zero current is full, and a cell cannot become full while staying below cv_min + R·I under current. The current taper therefore inevitably crosses the criterion when the battery is genuinely full, even if the requested charge voltage is never reached (e.g. low PV production days).
Cut-Off Cell Voltage source
The Cut-Off Cell Voltage select defines which cell voltage feeds the whole Cut-Off logic below (cell_v in this document):
Max Cell Voltage(default):cell_v = max_cell_v. Conservative, the end of charge depends on the highest cell.Average Cell Voltage:cell_v = battery_voltage / cell_count. The end of charge reflects the state of the whole pack, giving a consistent charge termination voltage from one day to the next. Recommended for packs built from unmatched cells (different internal resistances), packs with a runner cell, or a BMS that does not report its equalizing status.
Warning
With
Average Cell Voltage, the highest cell no longer stops the charge. Cell-level protection must be ensured byAuto CVLand/orAuto CCL, the BMSOVPremaining the last resort. If your inverter does not respect the requested charge voltage, only theAuto CCLis effective.
Cut-Off Charging Logic Diagram (what's happening in the yellow diamond)
Note
The diagram below is valid for other chemistries like Li-ion and LTO but with other CVmin and CVmax values.
Warning
This diagram no longer reflects reality and needs to be updated.
The logic evaluates the battery current first, in three zones:
1. Current deadband (current < 0.005C, ≈1.4 A on a 280 Ah pack) — the current is within sensor noise or PV starvation, the compensated equation is not meaningful. Three outcomes:
cell_v ≥ cv_minandSoC ≥ 95 %→ Cut-Off conditions valid. This is the fully charged at rest signature:cv_minis by definition the resting voltage of a full cell, so a battery that stops accepting current withcell_vabove it has completed its charge — without ever needing to reach the bulk voltage.cell_v < cv_min→ Bulk conditions valid: the battery cannot be full, any running timer is stopped.- otherwise → grey zone: no conclusion is drawn, the charge status is left unchanged.
2. Charging (current > deadband) — the Cut-Off conditions are valid when both:
cutoff_voltage ≥ cv_minwherecutoff_voltage = cell_v − cutoff_resistance × current(the compensated criterion, see the equation above);SoC ≥ 95 %(yambms_eoc_min_soc, configurable, max 98 %) — a safety net against premature Cut-Off caused by a runner cell or a transient voltage reading.
Otherwise the Bulk conditions are valid.
3. Discharging — the Bulk conditions are valid when cell_v < cell_bulk_v − cell_hysteresis_v (20 mV/cell by default). Otherwise nothing changes (grey zone).
The Bulk or Cut-Off conditions must hold continuously for 10s before the corresponding phase is entered. Transient states (cloud passages, load spikes) that flip the conditions back and forth never change the phase.
Once the Cut-Off phase is entered:
- if the BMS reports that cells are equalizing, the cut-off timer is stopped: the charge is held so the balancer can work;
- otherwise the cut-off timer starts (
180sdefault): if the Cut-Off conditions still hold when it expires, the EOC (End Of Charge) is declared; - in parallel, if the
EOC timerswitch is enabled, the EOC timer (30mindefault) guarantees that the Cut-Off phase ends at the latest when it expires, even if cells are still equalizing.
Returning to the Bulk phase stops both timers.
LFP Cut-Off Values
- Nominal : 3.20 V
- CV min : 3.37 V
- CV max : 3.65 V
To enter the Cut-Off phase while charging, cutoff_voltage ≥ cv_min and SoC ≥ 95 % must hold for 10s.
Reading example at 5A: the Cut-Off conditions become valid when cell_v reaches 3.47 V (the row where Cut-Off A. equals the instantaneous current). The Cut-Off V. column shows the compensated voltage for each cell_v, which must exceed cv_min.
Li-ion Cut-Off Values
- Nominal : 3.60 V
- CV min : 3.90 V
- CV max : 4.20 V
To enter the Cut-Off phase while charging, cutoff_voltage ≥ cv_min and SoC ≥ 95 % must hold for 10s.
LTO Cut-Off Values
- Nominal : 2.40 V
- CV min : 2.55 V
- CV max : 2.85 V
To enter the Cut-Off phase while charging, cutoff_voltage ≥ cv_min and SoC ≥ 95 % must hold for 10s.