The YamBMS Auto Temp-Based Current function is a software control designed to protect battery cells from damage due to charging or discharging at extreme temperatures.
It dynamically calculates a "Delta" (reduction value) that adjusts the configured maximum charge and discharge limits based on the thermal environment of the battery.
Lithium Iron Phosphate (LiFePO4) batteries have specific "C-rate" limits that change with temperature. For example, charging at 0°C may be prohibited or restricted to a very low current, while charging at 25°C allows for the full rated current.
This function automates that logic by:
- Monitoring the minimum and maximum cell temperatures.
- Filtering out sensor noise.
- Interpolating a safe C-rate from user-defined tables.
- Calculating the required current reduction (Delta).
Sequence of Operation
- Check Switch: Is the feature enabled?
- Validate Data: Are sensors online and reporting valid numbers?
- Filter: Apply EMA smoothing to the raw temperature values.
- Lookup: Find the C-rate for the current temperature.
- Calculate: Determine the current reduction needed.
- Apply: Round the result and update the relevant globals.
Core Logic
EMA Filter
Battery cells have significant thermal mass; their temperature does not change instantly. However, digital sensors often jitter between values (e.g., bouncing between 6.8°C and 6.9°C).
To prevent the charge current unnecessary fluctuations, an Exponential Moving Average (EMA) is used:
S_t = (\alpha \times Y_t) + ((1 - \alpha) \times S_{t-1})
Alpha (\alpha) - Set to 0.05. This provides a stable, slow-moving average that ignores minor sensor noise but tracks real thermal trends.
Adaptive Filtering - If the sensor jumps by more than 5°C (for example, during boot-up or BMS connection), the filter ignores the EMA logic and updates immediately to the new value to ensure safety.
Linear Interpolation
Auto Temp uses a pair of mapping tables (yambms_charging_rate_table & yambms_charging_rate_table) to define the relationship between temperature and C-Rate for both charging and discharging.
The interpolation function calculates values between defined points in these tables:
For example:
- Point A:
0^\circ\text{C}=0.0\text{C}(No charging) - Point B:
10^\circ\text{C}=0.1\text{C}(Slow charging)
If the actual battery temperature is 5^\circ\text{C}, the code determines that 5 is exactly halfway between 0 and 10, so it outputs 0.05\text{C}.
Logic Walkthrough
The function is written as a C++ lambda (a small, self-contained function) that takes two inputs: the mapping table (m) and the current temperature (x).
- Boundarys and checks
if (m.empty()) return 0.0f;
if (x <= m.begin()->first) return m.begin()->second;
if (x >= m.rbegin()->first) return m.rbegin()->second;
- Empty table: If the table isn't loaded, it returns 0.
- Lower bound: If the temperature is colder than the first mapping entry (e.g.,
-10^\circ\text{C}when the table starts at0^\circ\text{C}), it simply returns the rate for0^\circ\text{C}. - Upper Bound: If the temperature is hotter than the last mapping entry, it returns the rate for the highest temperature defined.
- Bracketing the input temperature value
auto it_upper = m.upper_bound(x);
auto it_lower = std::prev(it_upper);
The function looks through the mapping table to find the two points that encompass the current temperature.
For a temperature of 7^\circ\text{C}, it finds the entries for 0^\circ\text{C} (lower) and 10^\circ\text{C} (upper).
- The Slope Calculation
float x0 = it_lower->first, y0 = it_lower->second;
float x1 = it_upper->first, y1 = it_upper->second;
return y0 + (x - x0) * ((y1 - y0) / (x1 - x0));
This uses the standard slope-intercept formula (y = mx + b).
It calculates the slope (Rate of change): \frac{\text{Change in C-Rate}}{\text{Change in Temp}}, then multiplies that slope by the distance the current temperature is from the lower bracket.
Finally, it adds that result to the lower bracket C-rate.
Why Use Interpolation Instead of Simple Steps?
Without interpolation, current limits would jump abruptly when the cell temperature passes a threshold.
Stepped current limits:
4.9^\circ\text{C}=14.0\text{A}5.0^\circ\text{C}=33.6\text{A}
This creates sudden changes in requested current that can stress equipment.
Interpolated current limits:
4.9^\circ\text{C}=33.2\text{A}5.0^\circ\text{C}=33.6\text{A}
The current limit adjusts smoothly between C-rate thresholds as the battery temperature changes. This reduces current hunting and minimises equipment stress.
The Delta Calculation
Unlike some systems that overwrite the maximum current, this function calculates a negative delta to be applied to a configured current limit.
\text{Target Current} = \text{Allowed Rate} \times \text{Battery Capacity (Ah)}
\text{Delta} = \text{Target Current} - \text{Max Configured Current}
Example:
- Battery Capacity: 280Ah
- Configured Max Charge Limit: 140A
- Interpolated Rate at 4.9°C: 0.12C
- Calculation:
(0.12 \times 280) - 140 = -106.4\text{A} - Result: The system requests a reduction of 106.4A, effectively setting the limit to 33.6A.
Safety & Edge Cases
- The code contains a clamp that ensures the logic can only lower the current limit, never increase it beyond configured limits settings.
- If the
Temperature-based Current Limitationswitch is turned OFF, the Delta is immediately reset to 0 to prevent temperature based current restrictions. - If any critical sensor (temperature or capacity) returns NaN (Not a Number), the system defaults the Delta to 0 to prevent unpredictable behavior.
Configuration
The behavior is dictated by the following tables defined in the main YAML. These values represent the multiplier of the total Ah capacity (C-rate).
# +-------------------------------------------------------------------------
# | Temperature-based current limitation
# | Can be disabled via the switch "Temperature-based current limitation"
# | This factor is applied to the battery capacity (Ah), not the current
# | maximum charge/discharge current. For example : 280Ah x 0.5 = 140A
# +-------------------------------------------------------------------------
# Temperature °C -> Charge Rate (0.0C to 1.0C)
yambms_charging_rate_table: |
{
{ 0.0, 0.05 },
{ 5.0, 0.12 },
{ 10.0, 0.30 },
{ 20.0, 0.50 },
{ 25.0, 0.50 },
{ 45.0, 0.50 },
{ 50.0, 0.50 },
{ 55.0, 0.50 },
{ 60.0, 0.00 }
}
# Temperature °C -> Discharge Rate (0.0C to 1.0C)
yambms_discharging_rate_table: |
{
{-30.0, 0.00 },
{-20.0, 0.50 },
{-10.0, 0.50 },
{ -5.0, 0.50 },
{ 0.0, 0.50 },
{ 5.0, 0.50 },
{ 45.0, 0.50 },
{ 50.0, 0.50 },
{ 55.0, 0.50 },
{ 60.0, 0.00 }
}
These values can be adjusted as needed, including adding or removing rows - the function will handle these changes automatically.