Sleeper85 6085e6ff24 PYLON CAN 0x359 - Send Charge Over Current on bit 0, stop sending UnBalanced Cell (#345)
Charge Over Current was set with 0x80 in bytes 1 and 3, a copy of the
Discharge Over Current value of byte 0. PYLON V1 and V2, LuxPower and the
other 0x359 specifications put it on bit 0 of both bytes, which is also
where 0x35A already sends it. Bit 7 is undefined, so the inverter never
saw the alarm.

UnBalanced Cell was sent on bit 4 of bytes 1 and 3. PYLON V2 defines byte
1 bit 4 as an external communication timeout that stops charge and
discharge, so a cell imbalance alarm could stop the inverter. Byte 3 bit
4 is reserved. Neither is sent any more; cell imbalance is still sent on
0x35A.

The frame layout is the same in PYLON V1 and V2, so the fix applies to
both, and to LuxPower which shares frame 5.
2026-11-14 19:50:47 +01:00
..