The alarm bitmask was published only when the number of BMS in alarm equalled var_bms_counter, the number of configured BMS. But only combined BMS are counted in alarm, so with one BMS offline or missing a value the alarm could never be raised : the inverter received only the warning bits, and the "Alarm" text sensor showed "Warning". STEP 2 now compares with var_to_combine_bms_counter. An uncombined BMS is offline or has missing data, it does not count as "not in alarm". This matches the rest of the combiner, where charge and discharge are already decided by the combined BMS only. The "Alarm" text sensor no longer compares counters : it is derived from the published alarm and warning bitmasks, so it shows what is sent to the inverter. The comment on the alarm sensor said "bitwise AND", it is an OR.
12 KiB
YamBMS behavior
Shunt/BMS combine status
Combined / Can be combined : This status indicates whether the BMS or Shunt is currently combined.
In this example there are 3x BMS and 1x BMS is not combined (it is offline or is not sending correct data).
Shunt
Combine condition :
- the
Combineswitch is enabled - Shunt
Online StatusisON(the shuntVoltageis> 0)
If one of these two conditions is not respected, the shunt is automatically uncombined.
Important
In RS485 modbus
multi-node, if a server does not respond (cable or hardware failure) theOnline Statusof the shunt will be set toOFFand it will be uncombined.
As soon as you import a Shunt and it can be combined (see condition) the values Voltage, Current, Power and SoC of the shunt(s) will take precedence over the BMS values.
Note
If all BMS are
uncombinedthe shunt data will no longer be published.
If one shunt is used for multiple batteries, it is possible to provide the BMS IDs the shunt code with the variable bms_ids, example: bms_ids: '{1, 2, 3}'.
When the BMS IDs are provided to the shunt and one or more of the BMS are offline, the shunt Combine switch will be turned OFF.
This is helpful when one BMS/battery shuts down for a longer time. The SoC of the shunt will then not be correct anymore and this avoids that the batteries are
discharged further then wanted.
Note
You need to manually enable the
Combineswitch again if it was disabled automatically. If you do not want that behaviour, do not providebms_idsto the shunt.
BMS
Combine condition :
- BMS
Online StatusisON / Connected(to detect a loss of connection with the BMS e.g. cable, BMS OFF or dead) - The BMS
Battery Capacityis> 0(to ensure that the data received is correct)
If one of these two conditions is not met, the BMS is automatically uncombined.
Important
In RS485 modbus
multi-node, if a server does not respond (cable or hardware failure) theOnline Statusof the BMS will be set toOFFand it will be uncombined.
From YamBMS 1.5.1 :
The binary_sensor does not only represent the state of the charge/discharge switches but simply whether the charge/discharge is allowed. The value of binary_sensor is related to the status of the switches/alarms.
The errors_bitmask should not be a condition to combine a BMS anymore, let the BMS decide if the charge/discharge is allowed (its alarm system takes care of that).
The errors_bitmask continues to be analyzed to send warnings/alarms to the inverter.
The behavior of the Charging Instruction and Discharging Instruction sensors responsible for the instructions sent to the inverter will also be adapted. Alarm analysis will no longer be checked. If at least one BMS allows charging, charging can continue, if at least one BMS allows discharging, discharging can continue. This will also be based on the binary_sensor related to the state of switchs/alarms of the BMS.
If a BMS blocks charging or discharging, the permitted current is automatically reduced.
External balancer
If an external balancer is used instead of the BMS internal one, it can be combined with the BMS.
Behaviour for equalizing and balance trigger voltage:
- When no external balancer is present for a BMS or it is offline, the BMS values are used for
equalizingandbalance trigger voltage. - When an external balancer is present for a BMS and it is online, the BMS sensor data for
equalizingandbalance trigger voltageis overwritten by the external balancer sensor data.
State of Charge
The SoC is slightly manipulated before reaching 0% or 100%.
SoC 100% will be sent to your inverter only when the battery is fully charged (useful for some inverters stopping charging when the SoC reaches 100%).
SoC behavior:
- If
SOC < 99%real SoC is sent - Else if
the battery is fully chargedreal SoC is sent - Else SoC
98%is sent
LED Status & Diagnostic Codes
The system uses Synchronized Diagnostic Blink Codes. This allows the device to communicate specific fault categories visually without requiring a network connection.
1. System Healthy
If no faults are present, the LED indicates the system is alive.
- Pattern: 🟢 Green Pulse (1s)
\rightarrow⚫ OFF (1s). - Meaning: All linked components operational.
- Cycle Time: ~2.0 Seconds.
2. Component Fault
When a fault occurs, the cycle changes to a strict 3-part message structure.
| Phase | Color | Duration | Description |
|---|---|---|---|
| 1. Header | 🔵 Blue | 1.0s | "Attention." Marks the start of a error report cycle. |
| 2. Gap | ⚫ OFF | 0.5s | "Wait." A short pause to prepare for counting. |
| 3. Code | 🔴 Red | Variable | "Data." A set count of short Red blinks. |
Reading the Blink Code
The number of Red blinks corresponds to the Fault Category (see table below). To make counting easier, long codes are broken into groups of 4:
- 5 Pips:
* * * *...* - 9 Pips:
* * * *...* * * *...*
Category Reference Table
| Blinks | Category | Description |
|---|---|---|
| 1 | API / MQTT | API or MQTT communication failure. |
| 2 | BMS | Battery Management System communication failure. |
| 3 | INV CAN | Inverter CAN bus communication failure. |
| 4 | INV RS485 | Inverter RS485 bus communication failure. |
| 5 | SHUNT | Shunt communication failure. |
| 6 | BALANCER | Balancer communication failure. |
| 7 | NETWORK | No wifi or ethernet connection. |
| 8-16 | AUX 1-9 | Reserved for future expansion. |
Advanced Behaviors
Spotlight Mode
When a fault is active anywhere in the system:
- Fault LEDs: Display the Red error code.
- Healthy LEDs: Turn OFF during the "Code" phase This reduces visual noise, highlighting exactly which components requires attention.
Multi-Fault Rotation
If a single LED monitors multiple components (e.g., a LED monitoring both the BMS and the Shunt) and both fail simultaneously:
- Cycle 1: Displays BMS Code (2 Pips).
- Cycle 2: Displays Shunt Code (5 Pips).
- Repeat: The LED rotates through active faults one by one.
Monochromatic LEDs
For boards without RGB LEDs:
- Header: Solid on.
- Code: Blinking.
- Gap/Healthy: off.
Multi-LED Boards
For boards with multiple LEDs, it's possible to assign a specific led to a specific component. For example, led_1 for BMS 1, led_2 for canbus. See the section below for more details.
Configuration & LED Assignment
The system links specific hardware LEDs to software components using Substitutions in your YAML package configuration.
Each component package (BMS, canbus, etc.) includes a specific variable to define which LED should report its status.
Example Configuration
In your main YAML file, under packages, you assign the Light ID to the *_status_led_id variable.
In most cases, the default values can be used but some boards such as the LilyGo T-Connect have multi-LED functionality.
- path: 'packages/bms/bms_combine_JK_RS485_Modbus_bms_standard.yaml'
vars:
# Unique ID for this specific instance
bms_id: '1' # must be a number
bms_name: 'JK-BMS 1'
bms_address: '0x01' # BMS 1 DIP switch
# LINKING THE LED
# Set this to the ID of the light component defined in your ESPHome config.
# Example: 'esp_light', 'led_1', etc. The board config will show further details
bms_status_led_id: 'esp_light' # LED used to show status; default = esp_light, comment out to disable
CAN bus link
For the CAN bus link to be established with your inverter, the three conditions below must be met:
- At least
oneBMS iscombined - The YamBMS status must be
initialized - Your inverter sends an
ACK 0x305every1s(the link will be faulty if no ACK is received for5s)
If these conditions are not met, the application waits 30s before trying to connect again.
During boot or when switching from 0 to 1 combined BMS, the CAN bus starts after YamBMS initialization, which can take 30s...
Sending CAN frames continues without an inverter connected is problematic and will lead to ESP32 crash.
For this reason, if the inverter does not respond after 5s, the link is paused for 30s before attempting to re-establish the communication.
The Deye inverter sends the ACK (can_id 0x305) only when it receives the can_id 0x356.
- path: 'packages/yambms/yambms_canbus.yaml' # yambms_canbus_web_server.yaml
vars:
canbus_id: '1' # must be a number
canbus_name: 'CANBUS 1'
canbus_status_led_id: 'esp_light' # LED used to show status; default = esp_light, comment out to disable
# The CAN bus link will be paused for `30s` if the inverter does not respond with an ACK (can_id 0x305)
# before the end of the `canbus_link_timer` (5s by default).
canbus_link_timer: '5s'
# CAN setup
canbus_platform: 'esp32_can' # esp32_can / mcp2515
canbus_node_id: 'canbus_inverter_1' # CAN bus node to which your inverter is connected
canbus_bitrate: '500kbps' # Default : 500kbps
Warning & Alarms
If all combined BMS have alarms, the alarms are sent to the CAN bus as Protection Alarms.
If at least one combined BMS has no alarms, the alarms are sent to the CAN bus as Warning.
Only combined BMS are counted. A BMS that is not combined (offline, or with missing data) is ignored, so a single BMS in protection while the others are offline sends Protection Alarms.
Both text_sensor Alarm and Warning show the alarms/warnings currently transmitted to the inverter.
Each BMS transmits its alarms using the YamBMS errors_bitmask in the format below :
# +--------------------------------------+
# | YamBMS Errors Bitmask (16bit) |
# +--------------------------------------+
# Bit 0 General alarm 0000 0000 0000 0001 0x0001
# Bit 1 Battery high voltage alarm 0000 0000 0000 0010 0x0002
# Bit 2 Battery low voltage alarm 0000 0000 0000 0100 0x0004
# Bit 3 Battery high temperature alarm 0000 0000 0000 1000 0x0008
# Bit 4 Battery low temperature alarm 0000 0000 0001 0000 0x0010
# Bit 5 Battery high temperature charge alarm 0000 0000 0010 0000 0x0020
# Bit 6 Battery low temperature charge alarm 0000 0000 0100 0000 0x0040
# Bit 7 Battery high discharge current alarm 0000 0000 1000 0000 0x0080
# Bit 8 Battery high charge current alarm 0000 0001 0000 0000 0x0100
# Bit 9 Contactor alarm 0000 0010 0000 0000 0x0200
# Bit 10 Short circuit alarm 0000 0100 0000 0000 0x0400
# Bit 11 BMS internal alarm 0000 1000 0000 0000 0x0800
# Bit 12 Cell imbalance alarm 0001 0000 0000 0000 0x1000
# Bit 13 Reserved 0010 0000 0000 0000 0x2000
# Bit 14 Reserved 0100 0000 0000 0000 0x4000
# Bit 15 Reserved 1000 0000 0000 0000 0x8000