YamBMS behavior

Badge License: GPLv3 Badge Version GitHub stars GitHub forks GitHub watchers

Shunt/BMS combine status

Image

Combined / Can be combined : This status indicates whether the BMS or Shunt is currently combined.

In this example there are 3x BMS and 1x BMS is not combined (it is offline or is not sending correct data).

Shunt

Combine condition :

  1. the Combine switch is enabled
  2. Shunt Online Status is ON (the shunt Voltage is > 0)

If one of these two conditions is not respected, the shunt is automatically uncombined.

Important

In RS485 modbus multi-node, if a server does not respond (cable or hardware failure) the Online Status of the shunt will be set to OFF and it will be uncombined.

As soon as you import a Shunt and it can be combined (see condition) the values ​​Voltage, Current, Power and SoC of the shunt(s) will take precedence over the BMS values.

Note

If all BMS are uncombined the shunt data will no longer be published.

If one shunt is used for multiple batteries, it is possible to provide the BMS IDs the shunt code with the variable bms_ids, example: bms_ids: '{1, 2, 3}'. When the BMS IDs are provided to the shunt and one or more of the BMS are offline, the shunt Combine switch will be turned OFF. This is helpful when one BMS/battery shuts down for a longer time. The SoC of the shunt will then not be correct anymore and this avoids that the batteries are discharged further then wanted.

Note

You need to manually enable the Combine switch again if it was disabled automatically. If you do not want that behaviour, do not provide bms_ids to the shunt.

BMS

Combine condition :

  1. BMS Online Status is ON / Connected (to detect a loss of connection with the BMS e.g. cable, BMS OFF or dead)
  2. The BMS Battery Capacity is > 0 (to ensure that the data received is correct)

If one of these two conditions is not met, the BMS is automatically uncombined.

Important

In RS485 modbus multi-node, if a server does not respond (cable or hardware failure) the Online Status of the BMS will be set to OFF and it will be uncombined.

From YamBMS 1.5.1 :

The binary_sensor does not only represent the state of the charge/discharge switches but simply whether the charge/discharge is allowed. The value of binary_sensor is related to the status of the switches/alarms.

The errors_bitmask should not be a condition to combine a BMS anymore, let the BMS decide if the charge/discharge is allowed (its alarm system takes care of that).

The errors_bitmask continues to be analyzed to send warnings/alarms to the inverter.

The behavior of the Charging Instruction and Discharging Instruction sensors responsible for the instructions sent to the inverter will also be adapted. Alarm analysis will no longer be checked. If at least one BMS allows charging, charging can continue, if at least one BMS allows discharging, discharging can continue. This will also be based on the binary_sensor related to the state of switchs/alarms of the BMS.

If a BMS blocks charging or discharging, the permitted current is automatically reduced.

External balancer

If an external balancer is used instead of the BMS internal one, it can be combined with the BMS.

Behaviour for equalizing and balance trigger voltage:

  1. When no external balancer is present for a BMS or it is offline, the BMS values are used for equalizing and balance trigger voltage.
  2. When an external balancer is present for a BMS and it is online, the BMS sensor data for equalizing and balance trigger voltage is overwritten by the external balancer sensor data.

State of Charge

The SoC is slightly manipulated before reaching 0% or 100%. SoC 100% will be sent to your inverter only when the battery is fully charged (useful for some inverters stopping charging when the SoC reaches 100%).

SoC behavior:

  1. If SOC < 99% real SoC is sent
  2. Else if the battery is fully charged real SoC is sent
  3. Else SoC 98% is sent

LED Status & Diagnostic Codes

The system uses Synchronized Diagnostic Blink Codes. This allows the device to communicate specific fault categories visually without requiring a network connection.

1. System Healthy

If no faults are present, the LED indicates the system is alive.

  • Pattern: 🟢 Green Pulse (1s) \rightarrow ⚫ OFF (1s).
  • Meaning: All linked components operational.
  • Cycle Time: ~2.0 Seconds.

2. Component Fault

When a fault occurs, the cycle changes to a strict 3-part message structure.

Phase Color Duration Description
1. Header 🔵 Blue 1.0s "Attention." Marks the start of a error report cycle.
2. Gap ⚫ OFF 0.5s "Wait." A short pause to prepare for counting.
3. Code 🔴 Red Variable "Data." A set count of short Red blinks.

The number of Red blinks corresponds to the Fault Category (see table below). To make counting easier, long codes are broken into groups of 4:

  • 5 Pips: * * * * ... *
  • 9 Pips: * * * * ... * * * * ... *

Category Reference Table

Blinks Category Description
1 API / MQTT API or MQTT communication failure.
2 BMS Battery Management System communication failure.
3 INV CAN Inverter CAN bus communication failure.
4 INV RS485 Inverter RS485 bus communication failure.
5 SHUNT Shunt communication failure.
6 BALANCER Balancer communication failure.
7 NETWORK No wifi or ethernet connection.
8-16 AUX 1-9 Reserved for future expansion.

Advanced Behaviors

Spotlight Mode

When a fault is active anywhere in the system:

  1. Fault LEDs: Display the Red error code.
  2. Healthy LEDs: Turn OFF during the "Code" phase This reduces visual noise, highlighting exactly which components requires attention.

Multi-Fault Rotation

If a single LED monitors multiple components (e.g., a LED monitoring both the BMS and the Shunt) and both fail simultaneously:

  • Cycle 1: Displays BMS Code (2 Pips).
  • Cycle 2: Displays Shunt Code (5 Pips).
  • Repeat: The LED rotates through active faults one by one.

Monochromatic LEDs

For boards without RGB LEDs:

  • Header: Solid on.
  • Code: Blinking.
  • Gap/Healthy: off.

Multi-LED Boards

For boards with multiple LEDs, it's possible to assign a specific led to a specific component. For example, led_1 for BMS 1, led_2 for canbus. See the section below for more details.

Configuration & LED Assignment

The system links specific hardware LEDs to software components using Substitutions in your YAML package configuration.

Each component package (BMS, canbus, etc.) includes a specific variable to define which LED should report its status.

Example Configuration

In your main YAML file, under packages, you assign the Light ID to the *_status_led_id variable. In most cases, the default values can be used but some boards such as the LilyGo T-Connect have multi-LED functionality.

packages:
  bms:
    url: https://github.com/Sleeper85/esphome-yambms
    ref: main
    refresh: 60min
    files:
      - path: 'packages/bms/bms_combine_JK_RS485_Modbus_bms_standard.yaml'
        vars:
          # Unique ID for this specific instance
          bms_id: '1' # must be a number
          bms_name: 'JK-BMS 1'
          bms_address: '0x01' # BMS 1 DIP switch
          
          # 1. LINKING THE LED
          # Set this to the ID of the light component defined in your ESPHome config.
          # Example: 'esp_light', 'led_1', etc. The board config will show further details
          bms_status_led_id: 'esp_light' # led used to show status. Default = esp_light, comment out to disable

For the CAN bus link to be established with your inverter, the three conditions below must be met:

  1. At least one BMS is combined
  2. The YamBMS status must be initialized
  3. Your inverter sends an ACK 0x305 every 1s (the link will be faulty if no ACK is received for 5s)

If these conditions are not met, the application waits 30s before trying to connect again.

During boot or when switching from 0 to 1 combined BMS, the CAN bus link is established after 30s.

Extra infos

Sending CAN frames continues without an inverter connected is problematic and will lead to ESP32 crash.

During boot the CAN bus links are activated directly if at least one BMS is combined and the inverter responds to the sending of CAN frames within a 5s delay. This 5s delay represents the time during which the link is valid, this timer is reset each time an ACK 0x305 is received from the inverter. This 5s delay can be modified in the configuration when importing the canbus package.

  canbus1: !include
    file: packages/yambms/yambms_canbus.yaml
    vars:
      canbus_id: '1' # Must be a number
      canbus_name: 'CANBUS 1'
      canbus_node_id: 'canbus_node1'
      canbus_status_led_id: 'esp_light' # led used to show status. Default = esp_light, comment out to disable
      # The CANBUS link will be considered down if no response from the inverter (ID 0x305) for 5s
      canbus_link_timer: '5s'

If the inverter does not respond with an ACK 0x305 within this 5s delay the sending of CAN frames is paused for 60s this delay cannot be modified when importing the canbus package but you can modify it in the code if you need to.

BMS alarms

Image

If all BMS have alarms, the alarms are sent to the CAN bus as Protection Alarms.

If at least one BMS has no alarms, the alarms are sent to the CAN bus as Warning.

Both text_sensor Alarm and Warning show the alarms/warnings currently transmitted to the inverter.