YamBMS behavior

Badge License: GPLv3 Badge Version GitHub stars GitHub forks GitHub watchers

Shunt and BMS combination

Image

Combine status

Image

Combine Availability : This status indicates whether the BMS or Shunt meets the conditions to be combined.

Can be combined : This status indicates whether the BMS or Shunt is currently combined.

Shunt

Combine condition :

  1. the Combine switch is enabled
  2. the Voltage supplied by the shunt is > 0V

If one of these two conditions is not respected, the shunt is automatically decombined.

As soon as you import a shunt and it can be combined (see condition) the values ​​(Voltage, Current, Power and SoC) of the shunt(s) will take precedence over the BMS values.

BMS

Combine condition :

  1. the Combine switch is enabled
  2. BMS Charging or Discharging switch is enabled
  3. BMS is not in alarm

If one of these three conditions is not met, the BMS is automatically decombined.

BMS alarms

Important

This is the current behavior, it may not be perfect, feel free to communicate your ideas to improve it.

Image

The errors_bitmask values ​​are merged and then analyzed continuously even if the BMS is uncombined.

As long as at least one BMS is working normally the system will continue to work. YamBMS will display BMS alarms as Warning.

If all BMS are in alarm, they are all uncombined and in this case the sending of instructions on the CAN bus is also stopped. YamBMS will display BMS alarms as Alarm.

For the CAN bus link to be established with your inverter, the two conditions below must be met:

  1. At least one BMS is in service (the number of combined BMS must be > 0)
  2. Your inverter sends an ACK 0x305 every 1s (the link will be faulty if no ACK is received for 5s)

If these conditions are not met, the application waits 120s before trying to connect again.