Sleeper85 cb3b0eedba Installed Battery Capacity now follows a capacity change at runtime
The installed total was accumulated once per BMS per boot, latched by
bms<id>_combined_once, so a BMS reconfigured with a different capacity
kept contributing its boot value until the next reboot.

Each BMS now remembers the last capacity it contributed in
bms<id>_installed_capacity and applies only the difference to the total.

- the update runs in the can_be_combined branch, so an offline BMS simply
  stops updating its contribution, which stays in the total : the installed
  capacity still never shrinks on an uncombine, as before
- a BMS coming back with a different capacity is applied as a delta, with
  no double counting
- combined_once had no other reader and is removed

The total is deliberately not turned into a per-round accumulator reset in
the Global vars reset block like the other totals : its sensor is polled
independently of STEP 2 and its state is written straight into CAN frame
0x379 with no has_state() guard, so a transient zero would announce 0 Ah of
installed capacity to the inverter. See Design_decisions.md.
2026-11-08 23:08:33 +01:00
..
2024-10-07 18:25:33 +02:00