Design decisions
Some parts of the codebase look more verbose or more redundant than they need to be. They are deliberate. This page records why, so that a well-intentioned cleanup doesn't reintroduce a bug that took a long time to find.
Do not refactor anything listed here without discussing it first, and read the rationale before touching the code.
Cut-Off / EOC logic
File: packages/yambms/yambms_core.yaml
The End Of Charge condition is deliberately compound. It has to distinguish a genuine EOC from a charge current that is merely capped by low solar production. Collapsing it into a single threshold or voltage comparison reintroduces false EOC on overcast days.
The combiner pipeline
Files: packages/bms/bms_combine.yaml, packages/shunt/shunt_combine.yaml,
packages/yambms/yambms_core.yaml
Every BMS and Shunt package instance runs the same interval lambda, and they coordinate through
a shared counter rather than through any central loop. Each instance only acts on the tick where
var_to_combine_bms_number equals its own ${bms_id}, then increments the counter so the next
instance can run. yambms_core.yaml (STEP 2) waits until every device has been processed, then
resets the counters to 1 for the next round.
This is why bms_id must start at 1 and be contiguous. It is not a style rule and not only
about the bitmask index: with a gap in the numbering, the counter stops at the missing id, never
advances, and STEP 2 never fires. The whole pipeline deadlocks silently.
Include the BMS and Shunt packages in ascending id order. Out-of-order includes still converge, but spread one round over several intervals instead of completing in one.
can_be_combined is deliberately exhaustive
The condition in bms_combine.yaml checks every sensor the combiner will read. It is long on
purpose: a single missing or NaN value entering the totals corrupts the aggregate that drives
the inverter. Do not shorten it to a few representative checks.
Note that the checks are not uniform. Most use has_state(), but total_voltage and
battery_capacity use > 0 — a BMS reporting zero for those is treated as not ready rather than
as a valid reading. max_charge_current and max_discharge_current use >= 0: 0 A is a valid
limit that a BMS can announce, and it must not take that BMS out of the combination. A NaN still
fails the comparison, so a limit that was never received keeps the BMS uncombined.
Combined by contribution, combined continuously, uncombined
Three distinct scopes in the same lambda, and they are not interchangeable:
- By contribution —
total_installed_battery_capacityis a maintained total, not a per-round accumulator. Each BMS remembers the last capacity it contributed inbms${bms_id}_installed_capacityand applies only the difference to the total. So the installed capacity follows a capacity change made at runtime, without a reboot, while an offline BMS simply stops updating its contribution — which stays in the total. It represents the installed capacity and deliberately does not shrink when a BMS drops offline. - Not continuously — the combined counter is incremented on the transition into the combined state, not on every tick.
- Continuously — the totals, bitmasks and min/max values are recomputed every round.
total_installed_battery_capacity must never be turned into a per-round accumulator reset in the
Global vars reset block like the other totals. Its sensor is polled independently of STEP 2 and
its state is written straight into CAN frame 0x379 with no has_state() guard, so a transient
zero would announce 0 Ah of installed capacity to the inverter.
bms_seen_online_bitmask is never cleared
It records that a BMS has been online at least once since boot. shunt_combine.yaml uses it to
tell "this BMS is offline" apart from "this BMS was never there" — a shunt must not be
uncombined because of a BMS the user never installed.
Cell numbers are offset per pack
The combiner reports cell number + (${bms_id} × 100), so cell 8 of BMS 1 is reported as 108
and cell 3 of BMS 2 as 203. This makes the pack immediately identifiable in the dashboard. It
caps a pack at 99 cells, which is well beyond any realistic configuration.
A shunt uncombine turns the user switch off, and does not turn it back on
When a BMS mapped to a shunt goes offline, shunt_combine.yaml switches Combine enabled off
and records which BMS caused it, so the diagnostic State entity can say so. Re-enabling is
deliberately manual: coming back online does not automatically restore the combination, because
the SoC reference has to be trusted before it is used again.
The {0} sentinel in bms_ids
shunt${shunt_id}_bms_map defaults to '{0}' because the vector needs a non-empty initialiser,
and the loop skips id 0 (if (!bms_id) continue;). Do not "clean up" the zero — it is what
makes an unmapped shunt valid.
CAN frame catalogue
File: packages/yambms/yambms_canbus.yaml
Several can_id values are reused with different payloads depending on the protocol:
| CAN ID | Frame | Protocol |
|---|---|---|
0x359 |
5 | PYLON |
0x359 |
24 | Deye PCS |
0x371 |
11 | SEPLOS |
0x371 |
28 | Deye PCS |
A frame's identity is its internal frame number, never its CAN ID. Do not merge two blocks because they share a CAN ID — that would break both protocols at once.
Byte order is not uniform either: 0x373 sends min cell voltage before max, 0x361 sends max
before min. Both match their respective specifications. Do not "harmonise" them.
Frame sequencing
File: packages/yambms/yambms_canbus.yaml
Each protocol is defined as a sequence of frame numbers emitted on a fixed interval, so a full
cycle lasts interval × sequence length — from a few hundred milliseconds to over a second
depending on the protocol. Some inverters are sensitive to that cadence. Do not change the
interval to make protocols "consistent" with each other.
When adding a frame to a sequence, remember that the sequence length is tracked alongside the array. Keep the two in sync, or the new frame will silently never be emitted.
The update and telemetry services must never block the loop task
File: packages/yambms/yambms_service.yaml
http_request runs synchronously on the ESP32 loop task. ESPHome arms the IDF task watchdog at
5s with CONFIG_ESP_TASK_WDT_PANIC=y, and feeds it at most every 1 s, so any single blocking
call has a 4s budget before the device panics and reboots.
Two paths exceed that budget on a network that filters outbound traffic. Both were reproduced on an OPNsense firewall and measured on hardware:
| Path | Blocking time | Bounded by |
|---|---|---|
| Port 80 dropped silently | 4.5s | timeout, whose ESPHome default is 4.5s |
| Port 53 filtered (drop or reject) | 7.0 s, fixed | nothing — timeout does not cover DNS |
The 7s figure is the lwIP resolver retry ladder (1 + 1 + 2 + 3s over DNS_MAX_RETRIES), and
it is deterministic to a few milliseconds. A reject is not faster than a drop: lwIP's UDP API has
no error callback, so the ICMP unreachable is counted and discarded, and the query still runs its
full budget. Only an actual DNS answer — including NXDOMAIN from a local resolver — fails fast.
This is why three separate settings are needed, and none of them is redundant:
watchdog_timeout: 60sis the only thing that covers the DNS wait. It is never reached in normal operation, where a full request takes under 400 ms.timeout: 3sbrings the socket phase back under the 4s budget. It does not help the DNS case.- The failure counter (
yambms${yambms_id}_var_service_failures) is what stops the loop from freezing for 7s every 6h, forever, on a device that will never reach the internet.
my_network.is_connected() is not a reachability test — it only proves the device holds an IP.
It is kept as a cheap first filter, but the counter is the real guard. Do not remove it on the
grounds that the connectivity check above it "already handles this".
The counter is incremented from on_error, which fires only when no connection could be made.
An HTTP error status still fires on_response and resets the counter, which is correct: the
network worked, so there is no freeze to protect against.
The POST is guarded by an if on the counter rather than nested inside the GET's on_response.
Nesting would stack one blocking request inside another on a loop task whose stack is 8192 B by
default — see LOOP_TASK_STACK.md. It also avoids a second 7s freeze on
a filtered network, halving the worst case.
Reaching 3 failures disables both requests until reboot.
Two services, one counter
The two requests are gated independently, by substitution and therefore at compile time:
| Substitution | Request | What it does |
|---|---|---|
yambms_update_service |
GET | checks the latest published version |
yambms_telemetry_service |
POST | sends the node's configuration |
They share one counter, and that is deliberate: the counter measures whether the network is reachable, not whether a given endpoint answered. Both requests block the loop task the same way, so either one is a valid source of that signal.
This is why the POST carries its own on_error / on_response, which looks redundant next to
the GET's. It is not. With yambms_update_service: 'false' there is no GET, and without those
triggers nothing would ever increment the counter — the POST would freeze the loop for 7s every
6h forever, which is exactly the bug the counter exists to prevent.
The one thing the two services share besides the counter is
yambms${yambms_id}_var_service_round_failed: cleared at the start of every round, raised by any
request that could not connect. The POST is skipped when it is set, so a round that has already
frozen the loop once does not freeze it a second time for nothing.
Keep that flag separate from the counter. The counter is cumulative and spans rounds; the
question the POST needs answered is "did a request fail in this round", which is not the same
question. Expressing it as failures == 0 happens to work while the GET runs immediately before
the POST and always writes the counter, but it silently breaks with yambms_update_service: 'false': nothing resets the counter before the guard, so the POST would stop for good after its
first failed round, and the counter would sit at 1 without ever reaching the threshold that
disables the service.
The interval carries a startup_delay
An interval: does not wait a full period before its first run. The scheduler sets the first
execution at now + random(0, min(period / 2, 5s)), capped by MAX_INTERVAL_DELAY = 5000 — see
the first execution happens immediately after a random smallish offset comment in
core/scheduler.cpp. A 6h interval therefore fires within 5 seconds of setup().
Without startup_delay, that first request lands in the middle of boot: combiner init at
priority 600, the first CAN frames to the inverter, RS485 polling starting up. Whether it runs at
all comes down to a race with the WiFi association, since is_connected() is usually still false
that early. That race is also why the reported symptom was a reboot every 6h rather than a boot
loop — but it is a race, not a design, and a fast reconnect after OTA can win it.
startup_delay: 5min puts the request outside the boot window and makes the sequence
deterministic on a network that filters outbound traffic:
| t | What happens | failures |
|---|---|---|
| 5min | GET fails after 7s, POST skipped | 1 |
| 6h05 | same | 2 |
| 12h05 | same | 3 |
| 18h05 and later | condition is false, no request is made | 3 |
So a device that will never reach the internet freezes for 7s three times over 12 hours, then
never again. The counter is restore_value: no, so a reboot replays that sequence — acceptable
for a node meant to run for months, and the reason the threshold is not lower: a single transient
outage must not disable version checking for good.
A version check has no urgency, so the 5min delay costs nothing.
A derived sensor is published by its source, not polled
File: packages/base/device_base.yaml
esp32_uptime formats the value of esp32_uptime_sec for humans. It used to do so from its own
update_interval: 10s lambda, reading id(esp32_uptime_sec).state.
Two independent pollers reading one another is a race. Each starts with its own random offset in
[0, 5s) — see the startup_delay note above — so on roughly half of boots the text sensor ran
first and formatted a state that had never been published. That state is NaN, and the
float→int conversion saturates to INT32_MAX on Xtensa, which the formatter prints as
24855d 3h 14m 7s. It reached the dashboard, the LVGL label, and the telemetry POST, where it
was stored server-side as a real record.
The source's on_value now publishes the text sensor, and the lambda formats x — the value
that was just published. The failure mode is not guarded against, it cannot occur.
Do not convert it back to a polled lambda with a has_state() guard. The guard would work, but
it leaves two pollers where one is enough, and it puts the ordering question back in front of
whoever edits the file next.
esp32_date_time_now keeps its own poller, because it has no source sensor to hang a trigger on.
There the guard is now().is_valid(), and it is the right tool: the problem is an NTP sync that
may not have happened yet, not a scheduling order.
The inverter protocol is resolved once, never in the loop
Files: packages/yambms/yambms_brand_registry.yaml, packages/yambms/yambms_canbus.yaml,
packages/yambms/yambms_rs485.yaml
The protocol actually applied on a link is not readable from a single select. It is the result of
a resolution with two inputs: the Protocol select, and — when that one is on Automatic — the
Inverter brand select passed through the registry's mapping.
That resolution runs in a script, triggered at boot and on on_value of either select, and its
result is stored in canbus${canbus_id}_active_protocol / rs485${rs485_id}_active_protocol.
Everything else only reads that integer.
Do not inline the resolution back into the consumers. The 100 ms sequencing interval, the five
protocol branches and the four LuxPower payload tweaks would each redo a table lookup and a
series of std::string comparisons ten times a second, for a value that only changes when a user
touches a select.
Do not dispatch on active_index() either. That is what the code did before: active_index() == 5
meant LuxPower purely by convention of the option order, so reordering the select silently broke
four payload branches in different frames. The YB_PROTO_* constants are named, and the
conversion from option string to constant exists in exactly one place — the resolution script.
on_value is used and not set_action: TemplateSelectWithSetAction::control() fires the
set trigger before publish_state(), so a script called from set_action would read the
previous option.
The resolution must not run during setup
on_value also fires when the select restores its value, at setup_priority::HARDWARE (800).
The telemetry slot, on the other hand, is reserved in on_boot at priority: -100. Between the
two, the vectors in yambms_core.yaml are still empty, so the script would index element 0 of
an empty std::vector and the device would crash on every boot. The registry's std::function
globals are at HARDWARE too, so calling them that early is a race of its own.
canbus${canbus_id}_link_ready / rs485${rs485_id}_link_ready is what closes both holes: the
script returns immediately until the slot has been reserved, and the reservation raises the flag
then runs the script explicitly. Do not drop that guard on the grounds that the has_state()
check above it already protects the script — it does not, it only proves the selects have a value.
The YB_PROTO_* values are internal
They are never persisted, never published to Home Assistant and never sent to the telemetry
service — the label from global_inverter_protocol_label() is what leaves the device. So the
ranges can be renumbered or extended at any time with no impact on existing nodes.
The two invariants that do bind are elsewhere: the order of the select options, because
restore_value stores an index (append new brands and protocols at the end, never insert), and
the labels, because they carry the continuity of the collected telemetry.
Turning the RS485 link off means invalidating its proxies
File: packages/yambms/yambms_rs485_pylon.yaml
pylontech_rs485 is passive: it answers the inverter from the proxy sensors YamBMS feeds. Stopping
the 100 ms interval therefore does not stop the link — the proxies keep their last value,
update_state_from_sensors_() still returns true, and the component keeps answering with stale
data while refreshing rs485_status, which is why the status stayed ON.
The component's own fail-safe is a NaN on any of the eight sensors it checks. The else branch
of the interval publishes those NaN once per transition, guarded by
rs485${rs485_id}_proxies_valid so it does not run ten times a second.
Only those eight sensors matter — the ones read by update_state_from_sensors_(). Invalidating the
others would be harmless but pointless, and would hide which ones the contract actually depends on.
On RS485 the protocol is compiled, the brand only gates it
Files: packages/yambms/yambms_rs485.yaml, packages/yambms/yambms_rs485_pylon.yaml,
packages/yambms/yambms_rs485_voltronic.yaml
rs485_protocol picks the implementation at compile time, and each implementation declares what
it is in rs485${rs485_id}_compiled_protocol. In Automatic the resolution script applies that
value and never derives a protocol from the brand: a node can only speak what was compiled into
it, and resolving anything else made the diagnostics describe a protocol that was not running.
Voltronic and MPP Solar are the reason this cannot be a brand mapping. On recent firmwares,
parameter 05 offers both PYL and LIB on RS485, so either implementation is a valid choice
for the same inverter and the brand says nothing about which one was compiled.
LIB is the one exception. It is a Voltronic protocol and no other brand can use it, so in
Automatic a node compiled for LIB stays silent for any other brand, and Note says why.
Forcing LIB is still possible, because an explicit protocol always takes priority over the
brand. Rebranded inverters are expected to select Voltronic. MPP Solar is not a rebrand, which
is why it has its own entry.
Turning the LIB link off means moving its Modbus address
File: packages/yambms/yambms_rs485_voltronic.yaml
modbus_server has no off switch, and returning nothing from a read_lambda only turns the reply
into an exception frame, so the inverter still gets an answer on a link that should be silent.
ModbusServerHub::find_device_() matches the address on every request, so moving the server to
address 248 makes the hub drop the request instead. The 100 ms interval moves it back to 1
only while rs485${rs485_id}_active_protocol is LIB.
Do not replace this with reported charge and discharge limits of zero: the inverter would still see a battery, on a link the user believes is off.
Disabled unregisters the link instead of faulting it
File: packages/base/device_base_fault_registry.yaml
Turning a link off stops the frames, so the inverter stops acknowledging, the link timer expires
and the status binary sensor goes false. Fed straight into global_update_fault() that lights the
fault LED for something the user asked for.
The registry already had the right answer: state 2, which both the master mask and the health
report ignore. global_update_fault() only takes a bool, so it can write 0 or 1 and nothing
else — hence global_unregister_fault(), added alongside it.
Do not use Healthy for a disabled link. It would clear the LED just as well, but the health
report would print [ OK ] for a link that sends nothing, which is worse than the bug it fixes.
The guard exists in two places and both are needed: the resolution script applies it when the
protocol changes, and the status sensor's on_state applies it on every subsequent state change.
Without the second one the link timer would re-raise the fault a few seconds later.
A link left at Automatic with no brand selected is deliberately not unregistered — it faults.
That is the signal telling the user the node was never configured, which is the whole point of the
1.8.0 breaking change.
Both ACK triggers are registered
canbus.cpp matches a trigger on can_id and use_extended_id, so declaring 0x305 twice —
once standard, once extended — is not a conflict: only the one matching the received frame fires.
This is why the Schneider XW Pro extended ACK needs no configuration, and why the
canbus_extended_ack substitution was removed. Both triggers call the same script so the handler
is not duplicated.
A UART is declared by the package that consumes it
Files: packages/board/board_options_itf_uart_*.yaml, every package taking a *_uart_id
The main YAML names a UART once, in the vars: of the package that uses it, and that package
imports the matching board_options_itf_${xxx_uart_id}.yaml. It replaces a two-step declaration,
an uart_esp_N include followed by a !extend of the baud rate, which could not reach a WK2168
channel: those live under wk2168_spi[].uart[], so every consumer needed an _expander twin
without the uart: block.
One importer per UART
Two imports of the same UART fail with ID uart_esp_1 redefined, on an expander channel too. Keep
it that way. Sharing a UART at two speeds has no valid meaning, and with the old !extend it did
not fail: the extended value simply won, so an inverter link declared at 115200 silently ran at
the 9600 of a BMS package on the same UART.
This is why bus-level packages import the UART, not the per-BMS ones: a bus package is included once, the BMS packages on that bus several times.
Each package keeps its key, uart_baud_rate stays internal
Every package exposes its own key (rs485_uart_baud_rate, pace_modbus_baud_rate,
shunt_uart_baud_rate...) and maps it to uart_baud_rate in the vars: of the import. Do not
expose uart_baud_rate itself: with ${uart_baud_rate | default(...)} in every package, one value
in a root substitutions: block would override all the consumers of the node, defaults included.
The defaults live in that | default() and nowhere else:
- Not in
substitutions:. Package substitutions are merged into one global block, sobms_uart_baud_ratewould get the same value for JBD (9600), JK UART (115200) and JK Display (2400), with no error. - Not in the UART file. It does not know who imports it, and a wrong speed is valid
configuration that fails silently on the wire. This is what the old fixed
115200hid: the JK UART, JK sniffer and Junctek packages only worked because that value happened to suit them. - Not as a fixed value. A value written in the
vars:of the import takes priority over the one passed by the user, who is ignored without a message.
Leave | default() out when the speed depends on the installation (PACE, EG4, Seplos, BASEN): a
missing key then fails validation instead of picking a speed.
modbus_baud_rate is the exception that keeps its place in substitutions:: yambms_config.yaml
shares it between the nodes of a multi-node setup from the root.
flow_control is enabled by a var, so min_version is 2026.10.0
uart_flow_control_pin is passed like any other var of the import and reaches the UART file,
which includes board_options_itf_uart_flow_control.yaml only when it is defined. So no consumer
has to know about it.
flow_control_pin: ${uart_flow_control_pin} with an empty default is not an option, the UART
schema refuses a null pin. The condition: key of !include is what makes the pin optional, and
ESPHome 2026.8.0 ignores it: the file is included anyway and the configuration fails. Do not lower
min_version without replacing it.
This !extend is the last one on a UART. It is not exposed to the user, and it works whatever the
order of the packages.
Expander channels
uart_spi_N and uart_i2c_N are numbered like the PVbrain2 connectors: 0 to 3 on bridge 0,
4 to 7 on bridge 1. Do not shift them to start at 1, every existing wiring would move by one
channel.
Each channel adds itself with !extend uart_bridgeN, and the bridges are declared with an empty
uart: by board_options_itf_wk2168_spi.yaml or board_options_itf_wk2168_i2c.yaml.
A WK2168 channel has no flow_control_pin, so uart_flow_control_pin is ignored there, without a
message. Its RS485 transceivers must handle the direction automatically. The _talk_pin packages
are kept for that one case: they drive a plain GPIO from the component, which works on any UART.
Everywhere else uart_flow_control_pin replaces them, and the examples no longer show them.
The UART id must be readable when the !include filename is resolved. A value built from a
substitution declared in a package, such as uart_${uart_hub_bus}_3, is not, so write uart_spi_3.
Empirical constants
Some constants were found by trial on real hardware and must not be rounded or harmonised.