# YamBMS functions
|
||
|
||
[](https://www.gnu.org/licenses/gpl-3.0)
|
||
[](https://github.com/Sleeper85/esphome-yambms/releases/latest)
|
||

|
||

|
||

|
||
|
||
## CAN protocol
|
||
|
||
> [!IMPORTANT]
|
||
> You need to check if your inverter model is on the list of [supported inverters](Supported_devices.md#supported-inverter). In any case it must support one of the following `CAN` bus protocols.
|
||
|
||

|
||
|
||
Choose the CAN protocol that will be sent to your inverter and don't forget to configure your inverter for the protocol you choose.
|
||
|
||
The table below helps you choose the best protocol depending on your inverter brand.
|
||
Other configurations are possible, don't hesitate to communicate what works well for you.
|
||
|
||
| Inverter | Battery mode | CAN protocol |
|
||
| --- | --- | --- |
|
||
| Deye | Lithium 00 | PYLON 1.2 |
|
||
| GoodWe | LX U5.4-L | PYLON + |
|
||
| Sofar | Automatic | PYLON 1.2 |
|
||
| Growatt | CAN L52 | PYLON 1.2 |
|
||
| Solis | AoBo | SMA |
|
||
| LuxPower | Lithium 6 | LuxPower |
|
||
| EG4 | Lithium 6 | LuxPower |
|
||
| Victron | CAN-bus BMS LV (500 kbit/s) | Victron |
|
||
| MidNite Solar | PYLON | PYLON 1.2 |
|
||
| SMA | - | SMA |
|
||
|
||
## Charging settings
|
||
|
||

|
||
|
||
The `Charging status` represents the current charging phase, see the [Charging logic](Charging_logic.md).
|
||
|
||
The `Charging instruction` is defined based on the `Charging status` and allows the correct `Requested Charge Values` to be sent.
|
||
|
||
The `Float charge enabled` switch allows the battery to be kept fully charged at the end of the `Bulk` charge. The voltage used will be that of the `Float voltage` slider.
|
||
|
||
The `EOC timer enabled` switch ensures that the `Cut-Off` phase lasts maximum `30 min` (default value) even if your cells are still being equalized. If your cells are equalized, the `Cut-Off` phase will end at the earliest after `60s` (default value). This prevents the risk of staying in the `Cut-Off` phase for many hours if you have several batteries and they are poorly equalized.
|
||
|
||
> [!IMPORTANT]
|
||
> If you have **totally unbalanced batteries** and want to fix this problem, you can disable the `EOC timer` and let `YamBMS` balance your batteries, **this can take hours**. A well balanced battery does not need this timer enabled as the equalization phase will finish in less than 30 minutes.
|
||
|
||
The `Bulk voltage` slider allows you to set the voltage used during the `Bulk`, `Balancing` and `Cut-Off` phases.
|
||
|
||
The `Float voltage` slider allows you to set the voltage used after charging is complete if the `Float charge enabled` switch is enabled.
|
||
|
||
The `Inverter Offset V.` slider allows you to correct the inverter charge voltage, either because it does not respect the requested value or because your inverter is far from your batteries and there is a voltage drop. This allows you to reach the target `Bulk` or `Float` charge voltage by adding an offset.
|
||
|
||
### Max current (%)
|
||
|
||

|
||
|
||
The allowed charge or discharge current is automatically calculated based on the `OCP` values of your BMS. The `OCP` currents of the combined BMS (not in alarm) are added together and the requested current is a percentage `0~90%` of this value.
|
||
|
||
### ReBulk
|
||
|
||

|
||
|
||
There are two parameters to start a new `Bulk` phase. You can set a `Rebulk SoC` or a `Rebulk V.` value, only one of these conditions must be met.
|
||
|
||
If needed you can also force a `Bulk` charge with the `Force Bulk (top bal)` switch. The switch will automatically deactivate when your cells enter the `Balancing` phase.
|
||
|
||
### Request Force Charge
|
||
|
||

|
||
|
||
This function allows you to force a charge from `GRID` :
|
||
- when `SoC <= Start SoC` the forced charge start
|
||
- when `SoC >= Stop SoC` the forced charge stop
|
||
|
||
Works only with `PYLON`, `LuxPower` and `Victron` protocols.
|
||
|
||
## Auto functions
|
||
|
||
Thanks to [@MrPabloUK](https://github.com/MrPabloUK) for developing these features.
|
||
|
||
A [reference spreadsheet](https://docs.google.com/spreadsheets/d/1UwZ94Qca-DBP5gppzKmAjbMJYZGjR4lMwZtwwQR9wWY/edit?usp=sharing) has been created that shows how the `Auto functions` works.
|
||
|
||

|
||
|
||
## Auto CVL
|
||
|
||
> [!IMPORTANT]
|
||
> The `Auto CVL` function uses the `Balance Trig. Volt.` value of your BMS. `e.g. for LFP` : BTG=0.010V
|
||
|
||
When enabled, the `Automatic Charge Voltage Limit` feature will automatically reduce the `Requested Charge Voltage (CVL)` sent to the inverter when a cell starts to exceed the bulk target.
|
||
That way, the runner cell should be maintained at or near bulk (for example, 3.45v) and the balancer can start to bring up the lagging cells.
|
||
Controlling the CVL is the preferred option according to Victron and others, but it depends on how well your inverter behaves.
|
||
My Solis inverter is not great at CVL control, so it doesn't work well for me.
|
||
|
||
You can compare `Auto CVL` to cruise control in a car.
|
||
|
||
`Boost Charge V.` allows you to increase the charging voltage to charge your battery faster, the `Auto CVL` function will itself reduce the charging voltage at the end of charging so that it does not exceed the target voltage `Bulk Voltage`.
|
||
|
||
## Auto CCL & DCL
|
||
|
||
> [!IMPORTANT]
|
||
> The `Auto CCL` function uses the `OVP` value of your BMS.
|
||
> The `Auto DCL` function uses the `UVP` value of your BMS.
|
||
|
||
Regarding the new `Auto Charge/Discharge Current Limit`, this features has been introduced to hopefully prevent `OVP` and `UVP` alarms.
|
||
|
||
When enabled, the `Automatic Charge Current Limit` feature will automatically reduce the `Requested Charge Current (CCL)` sent to the inverter when a cell starts to exceed the bulk target.
|
||
This should prevent the runner cell from exceeding the max voltage cutoff, but doesn't maintain it at bulk voltage - instead it should keep it just below max cell voltage.
|
||
|
||
You can compare `Auto CCL` to a max speed limiter in a car.
|
||
|
||
`Auto DCL` works the same way when a cell approaching `UVP + 0.2`.
|
||
|
||
Current control should work with any inverter that uses `CAN` control.
|
||
|
||
## Requested Values
|
||
|
||

|
||
|
||
These 4 sensors allow you to see what is being requested of your inverter.
|
||
|
||
In the example below, we are in the `Float` phase at a voltage of `53.6V` and an `Inverter Offset V.` of `0.1V`. The `Requested Charge Voltage` is therefore `53.7V`.
|
||
|
||
The `Requested Discharge Voltage` is the `UVP + 0.2` value of your BMS multiplied by the number of cells, in this example (3V * 16).
|
||
|
||
The `Requested Charge/Discharge Current` is the `OCP` value of your BMS multiplied by the `Max current` percentage, in this example (150A * 80%).
|
||
|
||
## Inverter Heartbeat Monitoring
|
||
|
||

|
||
|
||
This feature allows you to monitor the heartbeat of your inverter (time between two ACK 0x305). This is useful for troubleshooting purposes and should not remain enabled continuously.
|
||
|
||
This heartbeat must be regular and depends on the selected `CAN protocol` and the behavior of the inverter. If the heartbeat is not regular this can show a problem on the inverter side or an overloaded ESP32.
|
||
|
||
The `Deye` inverter sends an ACK `0x305` in response to the reception of a CAN frame `0x356`. Knowing that CAN frames are sent every `100ms` and that the CAN protocol `PYLON 1.2` has 6 CAN frames, the heartbeat of the `Deye` inverter is `600ms`.
|
||
|
||
> [!IMPORTANT]
|
||
> Every `2h` Deye takes more than `3s` to respond and more than `5s` at midnight.
|
||
> This is what the `CANBUS Status` looks like when the `canbus_link_timer` is set to `3s`.
|
||
|
||

|
||
|
||
## Diagnostic
|
||
|
||
Useful information for troubleshooting.
|
||
|
||

|
||
|
||
## YamBMS version
|
||
|
||
This function lets you know if a new version of YamBMS is available, the check is done every 6 hours.
|
||
|
||

|