Auto CCL-DCL based on OVP-UVP
This commit is contained in:
1 parent
f79aca0a22
commit
f193e27e83
1 file changed
+4
-4
@@ -101,8 +101,8 @@ You can compare `Auto CVL` to cruise control in a car.
|
||||
## Auto CCL & DCL
|
||||
|
||||
> [!IMPORTANT]
|
||||
> The `Auto CCL` function uses the `OVPR` value of your BMS which must be higher than `cell_bulk_voltage` to work properly. `e.g. for LFP` : CVL=3.45V / OVPR=3.55V / OVP=3.65V.
|
||||
> The `Auto DCL` function uses the `UVPR` value of your BMS. `e.g. for LFP` : UVPR=3.00V
|
||||
> The `Auto CCL` function uses the `OVP` value of your BMS.
|
||||
> The `Auto DCL` function uses the `UVP` value of your BMS.
|
||||
|
||||
Regarding the new `Auto Charge/Discharge Current Limit`, this features has been introduced to hopefully prevent `OVP` and `UVP` alarms.
|
||||
|
||||
@@ -111,7 +111,7 @@ This should prevent the runner cell from exceeding the max voltage cutoff, but d
|
||||
|
||||
You can compare `Auto CCL` to a max speed limiter in a car.
|
||||
|
||||
`Auto DCL` works the same way when a cell approaching `UVPR`.
|
||||
`Auto DCL` works the same way when a cell approaching `UVP + 0.02`.
|
||||
|
||||
Current control should work with any inverter that uses `CAN` control.
|
||||
|
||||
@@ -123,7 +123,7 @@ These 4 sensors allow you to see what is being requested of your inverter.
|
||||
|
||||
In the example below, we are in the `Float` phase at a voltage of `53.6V` and an `Inverter Offset V.` of `0.1V`. The `Requested Charge Voltage` is therefore `53.7V`.
|
||||
|
||||
The `Requested Discharge Voltage` is the `UVPR` value of your BMS multiplied by the number of cells, in this example (3V * 16).
|
||||
The `Requested Discharge Voltage` is the `UVP + 0.02` value of your BMS multiplied by the number of cells, in this example (3V * 16).
|
||||
|
||||
The `Requested Charge/Discharge Current` is the `OCP` value of your BMS multiplied by the `Max current` percentage, in this example (150A * 80%).
|
||||
|
||||
|
||||