Auto CCL-DCL based on OVP-UVP

This commit is contained in:
Sleeper85 committed 2024-12-21 15:49:21 +01:00
1 parent f79aca0a22
commit f193e27e83
1 file changed
+4 -4
+4 -4
View File
@@ -101,8 +101,8 @@ You can compare `Auto CVL` to cruise control in a car.
## Auto CCL & DCL
> [!IMPORTANT]
> The `Auto CCL` function uses the `OVPR` value of your BMS which must be higher than `cell_bulk_voltage` to work properly. `e.g. for LFP` : CVL=3.45V / OVPR=3.55V / OVP=3.65V.
> The `Auto DCL` function uses the `UVPR` value of your BMS. `e.g. for LFP` : UVPR=3.00V
> The `Auto CCL` function uses the `OVP` value of your BMS.
> The `Auto DCL` function uses the `UVP` value of your BMS.
Regarding the new `Auto Charge/Discharge Current Limit`, this features has been introduced to hopefully prevent `OVP` and `UVP` alarms.
@@ -111,7 +111,7 @@ This should prevent the runner cell from exceeding the max voltage cutoff, but d
You can compare `Auto CCL` to a max speed limiter in a car.
`Auto DCL` works the same way when a cell approaching `UVPR`.
`Auto DCL` works the same way when a cell approaching `UVP + 0.02`.
Current control should work with any inverter that uses `CAN` control.
@@ -123,7 +123,7 @@ These 4 sensors allow you to see what is being requested of your inverter.
In the example below, we are in the `Float` phase at a voltage of `53.6V` and an `Inverter Offset V.` of `0.1V`. The `Requested Charge Voltage` is therefore `53.7V`.
The `Requested Discharge Voltage` is the `UVPR` value of your BMS multiplied by the number of cells, in this example (3V * 16).
The `Requested Discharge Voltage` is the `UVP + 0.02` value of your BMS multiplied by the number of cells, in this example (3V * 16).
The `Requested Charge/Discharge Current` is the `OCP` value of your BMS multiplied by the `Max current` percentage, in this example (150A * 80%).